In-row heat exchanger for cabinet cooling in containment systems

Pentair has extended its IT infrastructure portfolio with a new series of air/water heat exchangers. The Schroff Varistar SHX30 in-row heat exchanger has been specially designed for cooling cabinets with high thermal loads installed in an aisle containment. The heat exchangers are added to the cabinets as a modular unit within the containment and are scaled to optimally match the planned packaging density. Redundancy is also implemented.

  • Wednesday, 23rd October 2013 Posted 11 years ago in by Phil Alsop

The basic unit is 300 mm wide and can be supplied in different heights (2000 or 2200 mm) and depths (1000 or 1200 mm). It is simple to configure to suit the appropriate requirements of the IT structure using individual components (side panels, plinth, covers, top cover, etc.). As for cooling modules, the customer can choose between units with one power supply unit or two (redundancy) as well as water connection points at the top or bottom. The cooling units are each fitted with six hot swap-capable fans and are regulated by internal and external temperature sensors. For monitoring purposes, an Ethernet interface and a Web interface are provided. With a water inlet temperature of 12 °C and an air exit temperature of 24 °C the module delivers a cooling capacity of 34 kW.


The Schroff Varistar SHX30 in-row heat exchangers are configured from matched, modular off-the-shelf components from the Varistar program using Schroff's ServicePlus option and can then be delivered within 10 working days.